Underground Cable Installation Key Activity

Underground Cable Installation Key Activities that should be Followed in Site:

Installation of Underground Cables:

Before installation of underground cables in a nice and perfect way it is necessary to consider some points carefully like excavation of cable trenches, cable laying, cable joint bay and jointing, termination at both ends  and back-filling the cable trenches and reinstate the roads, then  testing and commissioning for final energizing the cable line.

To ensure the best quality work must engage the qualified personnel who have sufficient knowledge and experience in construction of underground cable for each part of work. For a dedicated project work it is important to keep mind taking appropriate approval from the employer or concern authority before execution or installation the cable.

Cable Drum Handling Procedure:

Cable drum shall be unloaded handle and in an approved manner on hard and well drained surface so that they must not sink. In no case shall the drum be stores flat i.e. with flange horizontal rolling of drums shall be avoided. For unreeling of cables, the drum shall be mounted on suitable jacks or on wheels. All possible care shall be taken during unreeling and laying to avoid dusting twist, kink or sharp bends.

Cable Bending Radius:


Cable bending radius is not same for all size and types of cable. So keep mind to follow the bending radii for cables as per manufacture’s recommendations. Cable trench especially in bending points should prepare carefully to comply with manufacture’s instruction and it should be strictly adhered to and necessary conducting medium shall be provided over the cable outer sheath for checking the healthiness of outer sheath applied.

Cable Trenches and Cable Joint Bay:

Cable trenches may be constructed for directly buried cables or concrete ready-made trench inside the compound as per employer requirement. For cable trench some key points like road crossing, rail -line crossing, existing power line, communication line or other utilities line crossing should be consider as per international or local standard.  For direct buried cable trench depth may vary site to site, normally an average depth of 1.5 meter from finished ground level for typical 132kV underground cable. Important for cable trench is sieved sand bedding, riddled soil cover, concrete protective covers back filling and compacting, route marker and joint marker.

Location of cable joint bay should consider the less traffic, road crossing, water storage, easy access ect.

Cable Laying Formation:

Cable laying formation may various types, very common used formation types are trefoil and flat formation.


 Cable Earthing and Bonding:

Earthling of cable metallic sheath with the cross bonding system and the sheath/screen bonding to the earth through disconnecting type link boxes at straight through joints and both end of cable terminations to avoid any induced voltage is also very important for underground cable system


Finally considerable for the system of cable jointing and termination work should be carryout by experienced jointers who shall have adequate skill and experience in jointing and termination for specified types and voltage grade of cable.

Comments

Popular posts from this blog

Star Delta Starter Line Diagram and Its Working Principle

ELECTRICAL DISTRIBUTION BOARD DB WIRING

SURGE ARRESTERS SPECIFICATION FOR 132 KV & 33 KV LINE

EARTH ELECTRODE RESISTANCE MEASUREMENT

MCB: MINIATURE CIRCUIT BREAKER OPERATION BASIC

CURRENT TRANSFORMERS –CT USING

ভুমিকম্পের কল্প কথা

Why Purge System Is Required For Refrigerant and How Does It Operate in Chiller Compressor

STEP AND TOUCH POTENTIAL: REDUCE ELECTRICAL HAZARD AND IMPROVE SAFETY AWARENESS

wazipoint

DMCA protected

The content is copyright protected to wazipoint and may not be reproduced on other websites.